All of the items here are obsolete, and are displayed here as a reminder of how electrical installations used to be done.
Principle of operation
Significant flaws
Obsolete Chilton earth leakage circuit breaker
Obsolete Crabtree earth leakage circuit breaker
Internally, the device consists of a double pole switch, a solenoid (trip coil), test button and resistor.
The E terminal connects to an earth electrode in the ground. The F terminal connects to the exposed metalwork (or frame) of the installation, normally the main earthing terminal in the fusebox.
In normal operation, the voltage between the E and F terminals is negligible. In the event of a fault between line and any exposed metalwork, the voltage on the F terminal will rise towards the line voltage. The E terminal will be at or near zero volts, and as there is now a potential difference between the E and F terminals, the trip coil will operate, opening the double pole switch.
The coil is selected so that a voltage of 50 volts will operate the trip.
The test button temporarily connects the test coil to line via a small resistor, simulating a fault. Note that the F terminal is disconnected when the test button is pressed - this is to avoid any voltages appearing on the exposed metalwork of the installation during the test.
While good in theory, in the real world, various situations can prevent the device from working.
Other connections to earth on the F side will short out the coil. This could include paths to earth via main protective bonding or via appliances such as immersion heaters and boilers.
The earth electrode must always have a reasonably low impedance, which can be difficult to achieve in well drained soils.
The earth electrode must be positioned so that it's resistance area does not overlap that of other electrodes, water pipes, gas pipes or other earthed metalwork. In a street with multiple properties, this will be very difficult to achieve. Overlapping with the resistance area of an electrode from a nearby installation can cause unwanted tripping due to faults in other properties.
Unlike a modern current operated RCD, these devices do not provide any protection against a person coming into contact with a live conductor. Faults between line and an earthed object such as a person will not cause any voltage to appear across the coil, and it will not trip.